| Supply |
|---|
| Connection |
Power Rail or terminals 11+, 12- |
| Rated voltage |
10 ... 40 V DC |
| Ripple |
within the supply tolerance |
| Rated current |
≤ 7 mA |
| Power dissipation/power consumption |
≤ 0.28 W |
| Input |
|---|
| Connection |
terminals 4+, 5- |
| Input resistance |
max. 20 MΩ (10 MΩ for .L- and .R version) , see also additional information |
| Transmission range |
0 ... ± 50 mV |
| Offset voltage/current |
≤ 5 µV / ≤ 5 nA |
| Output |
|---|
| Connection |
terminals 7+, 8- |
| Load |
Accuracy figures for infinite load impedance. Additional 0.03 % of span for a load resistance of 10 kΩ |
| Voltage |
0 ... ± 50 mV |
| Output resistance |
max. 3 Ω |
| Line fault detection |
-80 mV |
| Transfer characteristics |
|---|
| Trip value |
-3 db at 350 Hz |
| Absolute |
< 0.25 K at 40 V voltage supply |
| Rise time |
≤ 1 ms |
| Directive conformity |
|---|
| Electromagnetic compatibility |
Standards |
|
Directive 89/336/EEC |
on request |
| Ambient conditions |
|---|
| Ambient temperature |
-20 ... 60 °C (-4 ... 140 °F) |
| Mechanical specifications |
|---|
| Degree of protection |
IP20 |
| Mass |
approx. 125 g |
| Data for application in connection with hazardous areas |
|---|
| EC-Type Examination Certificate |
BASEEFA 03 ATEX 0076 ; for additional certificates see www.pepperl-fuchs.com |
|
Group, category, type of protection |
[EEx ia] IIC (Tamb = 60 °C) |
| Statement of conformity |
TÜV 99 ATEX 1499 X (observe statement of conformity) |
|
Group, category, type of protection, temperature class |
II 3G EEx nA II T4 |