NAMUR sensors
Security policy (edit with Customer reassurance module)
Delivery policy (edit with Customer reassurance module)
Return policy (edit with Customer reassurance module)
| General specifications | ||
|---|---|---|
| Switching function | Normally closed (NC) | |
| Output type | NAMUR | |
| Rated operating distance | 2 mm | |
| Installation | flush | |
| Assured operating distance | 0 ... 1.62 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.3 | |
| Reduction factor r304 | 0.85 | |
| Output type | 2-wire | |
| Nominal ratings | ||
| Nominal voltage | 8.2 V (Ri approx. 1 kΩ) | |
| Operating voltage | 5 ... 25 V | |
| Switching frequency | 0 ... 2000 Hz | |
| Hysteresis | 3 % | |
| Suitable for 2:1 technology | yes , Reverse polarity protection diode not required | |
| Current consumption | ||
| Measuring plate not detected | min. 3 mA | |
| Measuring plate detected | ≤ 1 mA | |
| Functional safety related parameters | ||
| MTTFd | 5887 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Compliance with standards and directives | ||
| Standard conformity | ||
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
|
| Standards | EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012 |
|
| Approvals and certificates | ||
| EAC conformity | TR CU 012/2011 | |
| FM approval | ||
| Control drawing | 116-0165 | |
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated ≤36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 2 m | |
| Core cross-section | 0.34 mm2 | |
| Housing material | Stainless steel 1.4305 / AISI 303 | |
| Sensing face | PBT | |
| Degree of protection | IP66 / IP67 | |
| Cable | ||
| Bending radius | > 10 x cable diameter | |
| Equipment protection level Ga | ||
| CE marking | [*PD-Z02585A*] | |
| ATEX marking | II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label. |
|
| Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions |
|
| Appropriate type | NJ 2-12GM-N... | |
| Effective internal inductivity | max. 30 nF ; a cable length of 10 m is considered. | |
| Effective internal inductance | max. 50 µH ; a cable length of 10 m is considered. | |
| Ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. Note:Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1. | |
| Equipment protection level Gb | ||
| CE marking | [*PD-Z02585A*] | |
| ATEX marking | II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label. |
|
| Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions |
|
| Appropriate type | NJ 2-12GM-N... | |
| Effective internal inductivity | max. 30 nF ; a cable length of 10 m is considered. | |
| Effective internal inductance | max. 50 µH ; a cable length of 10 m is considered. | |
| Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. | |
| Equipment protection level Da | ||
| CE marking | [*PD-Z02585A*] | |
| ATEX marking | II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label. |
|
| Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions |
|
| Appropriate type | NJ 2-12GM-N... | |
| Effective internal inductivity | max. 30 nF ; a cable length of 10 m is considered. | |
| Effective internal inductance | max. 50 µH ; a cable length of 10 m is considered. | |
| Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the surface temperature, and the effective internal reactance values can be found on the EC-type-examination certificate. The maximum permissible ambient temperature of the data sheet must be noted, in addition, the lower of the two values must be maintained. |
|
| General information | ||
| Scope of delivery | 2 self locking nuts in scope of delivery | |
| Use in the hazardous area | see instruction manuals | |
| Category | 1G; 2G; 1D | |