HiD2030 Pepperl+Fuchs SMART Transmitter Power Supply

$893.00

SMART Transmitter Power Supply HiD2030

  • 2-channel isolated barrier
  • 24 V DC supply (bus powered)
  • 2-wire SMART transmitters or current sources
  • Usable as signal splitter (1 input and 2 outputs)
  • Dual output 4 mA ... 20 mA or 1 V ... 5 V
  • Line fault detection (LFD)
  • Up to SIL 2 acc. to IEC 61508
Quantity
Last items in stock

  • Security policy (edit with Customer reassurance module) Security policy (edit with Customer reassurance module)
  • Delivery policy (edit with Customer reassurance module) Delivery policy (edit with Customer reassurance module)
  • Return policy (edit with Customer reassurance module) Return policy (edit with Customer reassurance module)
General specifications
Signal type Analog input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Supply
Connection SL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage 20.4 ... 30 V DC bus powered via Termination Board
Rated current 60 mA at 24 V, 20 mA output (per channel)
Power dissipation 1.05 W at 24 V (per channel)
Input
Connection side field side
Connection SL2: 5a(+), 5b, 7a(-); 1a(+), 1b, 3b(-)
Input current 4 ... 20 mA , current limit 26 mA typ.
Input resistance 40 Ω , for current source
Ripple 10 mV eff
Voltage min. 15.5 V at 20 mA
Communication pass-through of HART signal to safe area 
The current sink terminals 4, 7 and 5, 6 do not pass the HART signal to safe area.
Output
Connection side control side
Connection SL1: 8a(+), 7a(-); 10a(+), 9a(-)
Load 0 ... 650 Ω
Output signal 4 ... 20 mA or 1 ... 5 V (on 250 Ω, 0.1 % internal shunt)
Ripple 10 mV eff on a load of 250 Ω
Response time 70 ms , 10 ... 90 % step change
Signal level no fault: 1 mA ... 23.5 mA input current
fault detection: < 0.2 mA or > 24 mA input current
Fault indication output
Connection SL1: 6b
Output type open collector transistor (common to both channels) 
fault bus signal, collective error message
Transfer characteristics
Calibrated accuracy < ± 0.1 % of full-scale value (current output)
Influence of temperature < ± 0.01 %/ K
Frequency range communication channel: 0.5 ... 40 kHz within 3 db, (-6 db at 100 kHz), Tx to output and output to Tx,
suitable for use with SMART transmitters using HART or similar protocol
Influence of load < ± 0.1 % of full-scale value from 0 ... 650 Ω
Linearity < ± 0.05 % of full-scale value
Indicators/settings
Display elements LEDs
Control elements DIP-switch
Configuration via DIP switches
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibility NE 21:2006
For further information see system description.
Degree of protection IEC 60529
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20
Mass approx. 140 g
Dimensions 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch)
Mounting on Termination Board
Data for application in connection with hazardous areas
EU-Type Examination Certificate CESI 02 ATEX 086
Marking Ex-Hexagon II (1)G [Ex ia Ga] IIC , Ex-Hexagon II (1)D [Ex ia Da] IIIC
Certificate PF 11 CERT 2109 X
Marking Ex-Hexagon II 3G Ex nA IIC T4 Gc [device in zone 2]
Directive conformity
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
CSA approval
Control drawing 366-005CS-12B (cCSAus)
IECEx approval IECEx TUN 04.0012
Approved for [Ex ia] IIC
2 Items